Permissible operating modes of current transformers
Dec 23, 2022| (1) Allowable operating capacity. The current transformer should operate within the rated capacity specified on the nameplate. If the operation exceeds the rated capacity of the nameplate, the accuracy will be reduced, the measurement error will increase, and the meter reading will be inaccurate, which is the same as the voltage transformer.
(2) Allowable current on the primary side. The primary side current of the current transformer is allowed to run for a long time at no more than 1.1 times the rated current. If long-term overload operation, the measurement error will increase, and the winding will be overheated or damaged. The secondary side current of the current transformer is generally 5A or 1A, and the commonly used one is 5A. When the current transformer is in normal operation, its secondary side circuit is close to a short circuit state.
(3) The secondary side of the current transformer cannot be open circuited during operation. If the secondary side of the current transformer in operation is open, high voltage will appear on the secondary side, which will endanger the secondary equipment and personal safety. If the work needs to disconnect the secondary circuit (such as dismantling the instrument), the secondary side terminals should be reliably short-circuited with the connecting piece before disconnection.
(4) Both the secondary side and the iron core of the current transformer should be reliably grounded. (To prevent the primary high voltage from entering the secondary side when the primary and secondary insulation breakdown)
(5) The load impedance of the secondary side shall not be greater than the rated load impedance (to ensure the accuracy of the measurement)
(6) Pay attention to the polarity of the terminals of the current transformer when wiring
(7) TA must not be connected to the secondary side of the TV (so as not to make TA approximately open circuit and cause the danger of high voltage)
(8) When working, special personnel must be supervised, use insulating tools, and stand on insulating mats.