How to prevent open circuits on the secondary side of current transformers?
Dec 03, 2025| 1. Standardized Installation and Maintenance: Ensure secure secondary side wiring during installation and use test terminals to enhance reliability.
Regularly check wiring terminals, insulation condition, and grounding status, and promptly address any loosening or aging issues.
2. Avoiding Misoperation: Fuses are strictly prohibited in the secondary circuit to prevent accidental disconnection.
Avoid switching circuits unless absolutely necessary; use dedicated short-circuit tools when switching is required.
3. Equipment Selection and Design: Relay protection and measuring instruments should ideally share separate current transformers. If sharing is unavoidable, isolate them using an intermediate converter.
Secondary circuit conductors must possess sufficient mechanical strength to prevent open circuits due to vibration or tension.
4. Safe Operation and Protection: When working on live circuits, the secondary winding must be short-circuited with a short-circuit bar, and operation between the short-circuit terminals and the current transformer is prohibited.
Use insulated tools, set up safety barriers, and assign dedicated personnel for monitoring.
5. Temporary handling: Unused current transformers should be shorted at their secondary terminals and reliably grounded.