What to do in an emergency after a current transformer is open-circuited?
Dec 01, 2025| 1. Immediate Reporting and Protection Deactivation: Upon discovering an open circuit, immediately report to dispatch and deactivate any potentially malfunctioning protection devices.
If the ammeter displays abnormally or the protection device issues a disconnection signal, prioritize deactivating the relevant protection devices.
2. Load Reduction and Safety Preparation: Request a reduction in the primary load current. If the transformer is severely damaged (e.g., smoking, abnormal noise), the load must be transferred or the power supply deactivated.
Operators must wear insulated boots and gloves, use qualified insulated tools, and ensure at least two people work together.
3. Short-Circuiting the Fault Point: Short-circuit the secondary side at the nearest test terminal using a jumper wire. If sparks are generated during short-circuiting, the fault point is below the short-circuit point; if no sparks are generated, the fault point may be in the upstream circuit.
If the open circuit is at the transformer body terminal and cannot be short-circuited, request a power outage.
4. Troubleshooting and Repair
Inspect easily loosened parts (such as terminals, poor contact points). External problems can be addressed immediately; if the fault is internal (such as a damaged relay), report it to a professional.
If abnormal noise persists after short-circuiting, it indicates an internal open circuit, requiring power outage and repair.
5. Fire Handling
If a fire is caused by an open circuit, first disconnect the power supply, then use a fire extinguisher. Never use water to extinguish the fire.
Precautions: An open circuit on the secondary side creates a high-voltage hazard; never touch the open circuit point directly.
Continuously monitor meters during the repair process to prevent the fault from escalating.