How to regularly inspect and maintain the current transformer?

Aug 04, 2025|

1. Regular inspection
1. Appearance inspection: Regularly check whether the shell of the current transformer has cracks, deformation or corrosion, especially whether the insulation part is intact. At the same time, check whether the surface of the porcelain sleeve is clean, and the oil-immersed current transformer should have no oil leakage.
2. Connection part inspection: Check whether the terminal of the current transformer is loose, oxidized or corroded to ensure that the connection is firm.
3. Sealing inspection: For oil-immersed current transformers, check its sealing to ensure that there is no leakage.
4. Insulation resistance test: Use a megohmmeter to measure the insulation resistance between the primary winding and the secondary winding of the current transformer, and between the winding and the ground. In general, the insulation resistance should be greater than 1000MΩ.
5. Ratio test: Use a ratio tester to measure the actual ratio of the current transformer and compare it with the nominal ratio. The error between the actual ratio and the nominal ratio should be within the allowable range, usually ±0.5% to ±1%.
6. Polarity test: Use a polarity tester or DC method to check whether the polarity of the current transformer is correct.
7. Load test: Under rated current, measure the secondary side load of the current transformer to ensure that it does not exceed the rated load.
8. Error test: Use an error tester to measure the ratio difference and angle difference of the current transformer and compare them with the standard value. The ratio difference and angle difference should be within the allowable range, usually ±0.2% to ±1%.
9. Operation status check: Regularly check the operation status of the current transformer, including temperature, sound and vibration, to ensure its normal operation.
2. Daily maintenance
1. Regular cleaning: Regularly use a clean cloth or brush to remove dust, dirt and oil stains on the surface of the current transformer, and avoid using corrosive cleaning agents.
2. Check the grounding status: Ensure that the secondary circuit of the current transformer has no open circuit and the grounding status is good.
3. Record maintenance: After each maintenance, record the maintenance content, test results and treatment measures in detail, and establish a maintenance file.