Inspection and treatment method of open circuit and short circuit fault on secondary side of current transformer

Jul 04, 2022|

Since only a small impedance is allowed in the secondary circuit of the current transformer, it is close to the short-circuit state under normal working conditions, with very little sound, which is generally considered silent. Current transformer faults are often accompanied by sound or other phenomena. If the core threading screw is not clamped tightly, the silicon steel sheet will loosen and the alternating magnetic flux in the core will change. With the change of alternating magnetic flux in the iron core, the vibration amplitude of silicon steel sheet increases and gives out a buzzing sound. This sound does not change with the load and will be maintained for a long time. Under light load or no load, the end of some silicon steel sheets leaving the stack vibrates, which will cause a certain buzz. This sound is sometimes absent and disappears with the increase of line load.

When the open circuit current of the secondary circuit is 0, the impedance is infinite, and the secondary winding generates a high electromotive force, with a peak value of several thousand volts. Because the secondary circuit is closed when the current transformer is in normal operation, the magnetic flux generated by the magnetic potential on the secondary side demagnetizes the magnetic flux generated on the primary side. When the secondary side is open circuit, the demagnetized magnetic flux disappears, which increases the magnetic flux in the iron core and is in a serious saturation state. This is the change of magnetic flux with time, and the waveform is flat top wave. Because the induced electromotive force of the secondary winding is proportional to the change of magnetic flux, it is obvious that the iron core may overheat and burn out the current transformer. Due to the increase of magnetic flux density and non sinusoidal magnetic flux, the silicon steel sheet oscillates unevenly, resulting in large noise.

When the secondary side of the current transformer is open circuit, the personnel on duty should wear insulating shoes and gloves and short circuit the test terminal of the secondary circuit of the accident current transformer on the distribution cabinet for inspection and treatment. If the above measures are invalid, it is considered that there may be a fault in the current transformer, and it should be stopped using at this time. If the current transformer may cause the action of the protection device, the relevant protection device shall be stopped.

When the secondary winding or circuit of the current transformer is short circuited, the indication of the electric energy meter and power meter can be zero or reduced, and the relay protection device may malfunction or not operate at the same time. If the operator on duty fails to find out in time and still increases the load according to the normal situation, the equipment will be damaged due to unacceptable overload. After this kind of fault occurs, the load should be kept unchanged, the protective device that may malfunction should be stopped, and the maintenance personnel should be notified to eliminate it quickly.

If smoke or fire is found inside the current transformer, it should be cut off with a circuit breaker and put out the fire with sand or a fire extinguisher.