Problems needing attention in the operation of current transformer
Jul 01, 2022| 1. The secondary side of current transformer shall not be open circuit during operation. Once the secondary side is open circuit, it will be burnt due to excessive iron loss and high temperature, or the insulation will be broken down due to the increase of secondary winding voltage, resulting in the risk of high-voltage electric shock. Therefore, when replacing meters, such as ammeters, active meters, reactive meters, etc., the current circuit should be short circuited before replacing meters. After the meter is adjusted, connect it to the secondary circuit first, then remove the short wiring and check whether the meter is normal.
2. If the current transformer buzzes, check whether the internal core is loose, and tighten the core bolts.
3. The shell of the secondary side of the current transformer shall be reliably grounded.
4. When the insulation resistance of the secondary coil of the current transformer is lower than 10-20 megohm, it must be dried to restore the insulation before it can be used.