Minor problems that may arise in current transformer applications
Apr 17, 2023| 1) The insulation of the leakage current transformer is very thick, and some insulation is loosely wrapped, and there are wrinkles between the insulation layers. In addition, the vacuum treatment is poor, and the impregnation is not complete to form an air-containing cavity, which is easy to cause partial discharge faults.
2) The scale and placement of the capacitive screen do not meet the design requirements, and at least the capacitive screen is discharged. The capacitor plates are not smooth and flat, or even misplaced or broken, which damages the voltage equalization characteristics. Therefore, when the electric field strength along the surface of some solid insulation reaches a certain value, partial discharge will be formed.
The direct consequence of the above-mentioned partial discharge is to crack the insulating oil, generate a lot of wax between the insulating layers, and increase the dielectric loss. This kind of discharge has a cumulative effect. If it continues to develop, the gas analysis in oil may show the characteristics of arc discharge.
3) Because the insulating material is not clean or has high moisture content, surface discharge may occur on its surface. This situation is more common when the primary terminal lead discharges along the surface of the pad.
4) Some loose connections or potential suspension of metal parts will cause spark discharge. For example, the support nut of the primary winding is loose, causing the potential suspension of the shielding aluminum foil of the primary winding.
5) Loose splints, bolts, and nuts for secondary connections, loose grounding nuts for the last screen, and loose tap fastening nuts, etc., may increase the contact resistance and cause local overheating failures. In addition, improper handling of on-site protection should also be taken seriously. For example, if the transformer gets wet from water, although it may be related to the sealing structure and sealing material of the manufacturer, there are also problems of protection and management. Generally speaking, the on-site vacuum degassing is insufficient or the vacuum drying is not carried out during maintenance, resulting in the dissolved gas in the oil being easily saturated or the residual air bubbles and high moisture content in the oil-paper insulation. All of these will leave potential safety hazards to the equipment.