Prevention of Open Circuit of Electrical Current Transformer Secondary Circuit

Feb 05, 2022|

(1) Short-circuit protection equipment such as fuses cannot be installed in the secondary circuit;


(2 The secondary circuit is not allowed to switch, if it is necessary to switch, it is necessary to take effective measures to prevent open circuit;


(3) One Electrical Current Transformer cannot be used together with the relay protection and the measuring instrument. If it is necessary to use it, the transformer needs to be connected in the middle of the measuring instrument;


(4) For the Electrical Current Transformer that has been installed but not in use, the terminals need to be short-circuited and grounded;


(5) When the terminal of the secondary circuit is selected, the test terminal should be selected;


(6) The mechanical strength of the connecting wire of the secondary circuit should be guaranteed.