Wiring guidelines for current transformers
Feb 20, 2023| a. The current transformer cannot allow secondary open circuit
The current transformer manufacturer solemnly warns everyone not to open the circuit twice when installing the current transformer, otherwise it will lead to very serious consequences. It will cause the iron core of the current transformer to accumulate a large amount of heat, and even burn the current transformer. The second is that the secondary open circuit will increase the number of windings of the current transformer coil, and its induced voltage will be much higher, which may cause breakdown of equipment and endanger the lives of workers.
b. The secondary side of the high-voltage current transformer must have one end that needs to be grounded
Because the primary side of the high-voltage current transformer is in a high-voltage state, if the middle of the primary and secondary coils is in a high-voltage breakdown due to the decline in insulation performance, at this time, when the primary side of the high-voltage current transformer is grounded, the high voltage will be introduced into the ground. It can guarantee the safety of the equipment and the safety of the staff.
c. The measurement and protection port of the current transformer cannot be connected incorrectly
Because the measurement and protection ports are different according to the design thickness of the iron core, if they are connected incorrectly, the data measured by the current transformer during normal operation will not be reliable.