Principles of use of current transformers

Jan 23, 2023|

1. The wiring of the current transformer should follow the principle of series connection: that is, one winding resistance is connected in series with the circuit under test, while two winding resistances are connected in series with all instrument loads.

2. According to the magnitude of the measured current, select an appropriate transformation ratio, otherwise the error will increase.

At the same time, both ends must be grounded to prevent that once the insulation is damaged, one high voltage side becomes two low voltage sides, causing personal and equipment accidents.

3. The secondary side is absolutely not allowed to open circuit, because once the circuit is open, the primary current I1 will all become magnetizing current, causing φm and E2 surges, resulting in excessive saturation and magnetization of the iron core, serious heating or even burning of the coil, and at the same time the oversaturated magnetization The magnetic circuit increases the error. When the current transformer is working normally, current coils such as measuring instruments and relays are connected in series on both sides. The impedance of the current coils such as measuring instruments and relays is very small, and the two sides are similar to short circuits. The magnitude of the CT secondary current is determined by a single current, and the two currents generate The magnetic potential is the balance of the magnetic potential of a single current.

If it is suddenly opened, the excitation electromotive force changes from a small value to a large value, and the magnetic flux in the iron core presents a severely saturated flat top wave, so the windings on both sides will induce a high peak wave when the magnetic flux is zero , whose value can reach thousands or even tens of thousands of volts, endangering the safety of workers and the insulation performance of instruments. In addition, the open circuit on both sides makes the voltage on both sides as high as hundreds of volts, which will cause electric shock accidents once they are touched. Therefore, the current transformers on both sides are equipped with short-circuit switches to prevent open circuits on both sides. During use, the circuit load should be removed immediately after two open circuits, and then power off. After everything is processed, it can be used again.

4. In order to meet the needs of measuring instruments, relay protection, circuit breaker fault judgment and fault filtering device, install There are 2~8 secondary current transformers.

5. The installation position of the protection current transformer should be set as far as possible according to the non-protection area of the main protection device. For example, if there are two sets of current transformers and the location permits, they should be installed on both sides of the circuit breaker so that the circuit breaker is within the range of cross protection

6. In order to prevent the bus failure caused by the flashover of the socket of the column current transformer, the current transformer is usually arranged at the outlet of the circuit breaker or the side of the transformer.

7. In order to reduce the damage caused by the internal fault of the generator, the current transformer used for automatic adjustment of the excitation device should be arranged on the outlet side of the generator stator winding. In order to facilitate the analysis and detection of internal faults before the generator is incorporated into the system, the current transformer used for measuring instruments should be installed on the neutral point side of the generator.