What are the common causes of current transformer sealing problems?
Feb 14, 2025| 1. Aging and damage of sealing materials
Natural aging: Sealing materials (such as rubber gaskets, sealants, etc.) will age naturally over time. Long-term exposure to air will affect the rubber material by factors such as oxygen and ultraviolet rays, resulting in the breakage of the rubber molecular chain, reduced elasticity, hardening, cracking, etc. For example, ordinary rubber gaskets may lose their sealing properties due to aging after several years of use in outdoor environments.
Chemical erosion: If the current transformer is installed in an environment with chemical pollution, the sealing material may be corroded by chemicals. For example, near chemical companies, acidic or alkaline gases in the air may react chemically with the sealing material. For oil-immersed current transformers, additives in the insulating oil may also affect the sealing material and reduce its performance.
Mechanical damage: During the installation and maintenance of the current transformer, or due to external factors such as collision and vibration, the sealing material may be mechanically damaged. For example, when installing the sealing gasket, if it is accidentally scratched by a tool, or if the sealing part is squeezed by severe vibration during transportation, the sealing material may be damaged or cracked.
2. Loose connection parts or poor sealing
Loose bolts: The connection of the current transformer housing and other parts is usually fixed by bolts. During operation, due to long-term vibration (such as being close to traffic arteries, large equipment operation, etc.) or thermal expansion and contraction, the bolts may gradually loosen. Loose bolts will cause gaps in the connection parts and destroy the sealing effect. For example, when the temperature rises, the transformer housing expands. If the bolts do not have enough pre-tightening force, gaps will be generated between the connection surfaces.
Uneven sealing surface: If the sealing surface of the connection part is uneven, it will also affect the sealing effect. During the manufacturing process, if the processing accuracy of the sealing surface is not enough, or the sealing surface is contaminated during installation (such as dust, impurities, etc.), the sealing surfaces will not fit tightly. For example, if the installation surface of the sealing sleeve of the input and output terminals is uneven, it may cause poor sealing, allowing external moisture or impurities to enter the transformer.
3. Temperature changes and pressure fluctuations
Effect of temperature changes: During the operation of the current transformer, the ambient temperature and its own heating will cause temperature changes. Temperature changes will cause the gas or liquid inside the transformer to expand or contract. For example, for an oil-immersed current transformer, when the oil temperature rises, the volume of the oil will expand. If there is not enough expansion space or the sealing system cannot adapt to this change, it may cause damage to the sealing components, such as the sealing gasket being squeezed out or broken.
Effect of pressure fluctuations: In some current transformers with pressure (such as SF6 gas-insulated current transformers), pressure fluctuations are an important factor affecting the seal. If the internal pressure is too high (such as when the temperature rises suddenly or the gas is replenished too much), it may exert excessive pressure on the sealing components, causing the sealing components to deform or damage. On the contrary, if the pressure is too low (such as when a gas leak occurs), the outside air may enter the transformer through tiny gaps and destroy the internal insulation environment.
4. Manufacturing process defects and quality problems
Irrational sealing design: During the design stage of the current transformer, if the sealing design is unreasonable, sealing problems are likely to occur. For example, the sealing gasket is improperly selected, and its size and material do not meet the working environment and pressure requirements of the transformer; or the sealing structure is too complicated, which is prone to poor sealing during the manufacturing process.
Lax quality control: During the manufacturing process, if there is no strict quality control, some transformers with sealing defects may flow into the market. For example, during the assembly process, the sealing parts are not strictly inspected and tested, resulting in bubbles, gaps and other problems in the sealing parts, and these transformers are prone to sealing failures during operation.