May 29, 2021| The magnitude of the secondary load impedance of the current transformer has a great influence on the accuracy of the transformer. This is because the secondary load impedance of the current transformer is greatly increased. When the allowable secondary load impedance is exceeded, the value of the excitation current is greatly increased. When the iron core enters a saturated state, most of the primary current is used to provide the excitation current. The error of the transformer is greatly increased, and its accuracy is reduced.
When the system is operating normally or there is a short circuit outside the differential protection range, the current value of the current transformer at both ends of the differential protection is the same as the phase value, and there should be no current flowing into the differential relay. But in fact, the characteristics of the two sets of current transformers are different. It may be exactly the same, the excitation current will be different, the secondary current will not be the same, the relay will flow unbalanced current. In order to reduce the unbalanced current, it is necessary to improve the structure of the current transformer to prevent its saturation, or to choose a special silicon steel sheet with low loss to make the iron core and increase the iron core section.