What are the specific methods for detecting the error of current transformers?
Oct 22, 2024| 1. Comparison method:
Self-test circuit: When the rated transformation ratio of the transformer to be tested is 1, the self-test circuit can be used for detection. Connect the primary winding and secondary winding of the transformer to be tested, and measure the ratio of the output current of the secondary winding to the input current of the primary winding to determine whether the error of the transformer is within the allowable range.
Comparison circuit: Generally, the comparison circuit is used for detection. Compare the transformer to be tested with a standard transformer of known accuracy level, and calculate the error of the transformer to be tested by measuring the difference in the output current of the two transformers. The standard should be two accuracy levels higher than the transformer to be tested. If there is no standard with two higher levels, a standard with one level higher than the transformer to be tested can also be used as a standard, but the error of the transformer to be tested should be included in the error of the standard.
Comparison circuit for symmetrical branch grounding: When the accuracy level of the current transformer used by the instrument under test is 0.1 or above, and the rated primary current is small (for example, less than 1A), the primary circuit should be indirectly grounded through a symmetrical branch or other methods. First, put the switch in the appropriate position, adjust the resistance and capacitance until the indication of the high-impedance millivoltmeter is the smallest, and the L1 terminal is close to the ground potential.
2. Difference method:
Measurement of non-traditional current transformer current output error circuit using the difference method principle: Use the difference method principle measurement device to measure the circuit of non-traditional current transformer current output error. The error measurement device in the figure is a current ratio meter type, and the galvanometer is connected in parallel to the differential current loop. When the current micro-difference source is adjusted to make the galvanometer indicate balance, the current of the differential current loop is close to zero.
Measurement of non-traditional current transformer voltage output error circuit using the difference method principle: Use the difference method principle measurement device to measure the circuit of non-traditional current transformer voltage output error. The error measurement device is of AC potential difference type. The galvanometer is connected in series in the differential pressure loop. When the voltage differential source is adjusted to make the galvanometer indicate balance, the current in the differential pressure loop is close to zero. S is a low-inductance shunt with an accuracy of not less than 0.02. The secondary current of the current standard device is converted into a voltage with the same nominal value as the secondary output of the tested transformer, and then the error is measured according to the impedance bridge principle.
DC method: Use a 1.5-3V dry battery to connect its positive pole to the primary coil L1 of the transformer, L2 to the negative pole, the secondary side K1 of the transformer to the positive pole of the milliammeter, and the negative pole to K2. After the wires are connected, close K to make the milliammeter pointer positive, and open it to make the milliammeter pointer negative, indicating that the terminal of the transformer connected to the positive pole of the battery and the terminal connected to the positive end of the milliammeter are of the same polarity.
3. AC method:
Current and voltage method: By passing the test current through the secondary side of the current transformer, measuring the voltage on the secondary side, calculating the secondary impedance, and then analyzing the error.
Volt-ampere characteristic test: During the test, the CT primary circuit is open, and the test voltage and current are passed through the secondary side of the current transformer to measure the volt-ampere characteristic curve. It is generally required to measure and record to the saturation point. The ammeter should be an electromagnetic or electric instrument. When analyzing the error, the low-value curve of the volt-ampere number of phases A, B, and C should be taken.
In addition, when performing current transformer error detection, the following matters need to be noted:
Detection environmental conditions: The ambient temperature has a great influence on the error of the current transformer, so the detection should be carried out within the specified temperature range. Generally speaking, the error of the current transformer should meet its error performance requirements at an ambient temperature of -25℃-55℃. The humidity of the detection environment should also be controlled within a certain range to avoid the influence of humidity on the equipment. The detection site should avoid the influence of interference sources such as strong magnetic fields and electric fields to ensure the accuracy of the test results.
4. Requirements for testing equipment:
Standards: Standard transformers or other current ratio standards used as calibrators must meet the following requirements:
Standards should be two accuracy levels higher than the transformer to be tested. If there is no standard with two higher accuracy levels, a standard with one higher accuracy level than the transformer to be tested can also be used as a standard, but the error of the transformer to be tested should be included in the error of the standard;
During the calibration cycle, the error change of the standard shall not exceed 1/3 of its allowable error;
Standards must have a valid calibration certificate. The difference between the secondary load during use and the load marked on the certificate shall not exceed ±10%.
Error measuring device: The measurement error caused by the measuring device shall not be greater than 1/10 of the allowable error of the transformer to be tested, of which the measurement error caused by the sensitivity of the device shall not be greater than 1/20, and the measurement error caused by the minimum scale value shall not be greater than 1/15.
Monitoring ammeter: The accuracy level of the monitoring ammeter shall not be lower than level 1.5, and the internal impedance of the ammeter shall remain unchanged in all indication ranges.
Current load box: When the ambient temperature is 23±5℃, at rated frequency, the current load box is within the range of 5%-120% of the rated current, and the operating error of the load box resistance and reactance shall not exceed ±3%.
Power supply and regulation equipment: The power supply and regulation equipment should have sufficient capacity and adjustment fineness, and should ensure that the power supply frequency is between 49.5-50.5Hz, and the waveform distortion factor shall not be greater than 5%.
Detection cycle: The cycle of current transformer error detection needs to comprehensively consider multiple factors, such as relevant standards and specifications, the type and purpose of current transformers, the use environment and conditions, the operation history and maintenance, the importance and reliability requirements of the equipment, etc. Generally speaking, the calibration cycle of current transformers for standard measurement is 2 years. For current transformers in electric energy metering devices used for trade settlement, there may be more stringent detection cycle requirements. The specific detection cycle should be determined based on the actual situation, comprehensively considering the above factors, and referring to the equipment manufacturer's recommendations and relevant technical specifications.