What problems should be paid attention to during the use of Electrical Current Transformer
Oct 16, 2021| ①The secondary side of the Electrical Current Transformer must not be open during operation. Once the secondary side is open, it will burn out due to excessive iron loss and high temperature, or the voltage of the secondary winding will rise and the insulation will break down, resulting in the risk of high-voltage electric shock. Therefore, when changing the meter, such as changing the ammeter, active meter, reactive meter, etc., the current loop should be short-circuited before the metering meter is replaced. When the meter is adjusted, the manufacturer of Electrical Current Transformer first connects it to the secondary circuit, then removes the short wiring and checks whether the meter is normal.
② If sparks are found when the short-circuit wire is removed, and the Electrical Current Transformer is open at this time, it should be re-short-circuited immediately, and the short-circuit wire can be removed only when it is found that there is no open circuit in the metering instrument loop. When removing the short circuit of the Electrical Current Transformer, you should stand on the insulating pad. In addition, consider deactivating the protection device of the Electrical Current Transformer circuit. After the work is completed, the protection device can be put into operation.
③If the Electrical Current Transformer has a buzzing noise, check whether the internal iron core is loose, and then tighten the iron core bolts. (3) One end of the secondary side of the Electrical Current Transformer, and the shell must be reliably grounded.
④When the insulation resistance of the secondary side coil of the Electrical Current Transformer is lower than 10-20 megohms, it must be dried to restore the insulation before it can be used.