High Quality Current Sensor Transformer with Slight Drift

High Quality Current Sensor Transformer with Slight Drift

The CT can be mounted on an existing panel, such as a control center or load center, to measure or monitor wattage. These CTs can be installed without disassembling existing cables for easy installation.

  • Product Introduction
Our Open Circuit Current Transformer, Ground Fault Protection Current Transformer, High Current Center Through Current Transformer, which are designed and made based on our customers' requirements, are praised through our untiring efforts and hard work. Our company has maintained a stable and long-term business relationship with foreign major manufacturers and foreign well-known large-scale spot stockers. Do the best brand, do the best quality products, do the best after-sales service is our purpose. Our company has always advocated the principle of consumer first.

67


Description:

¨   50/60 Hz,Single Phase,AC Current Sensor

¨   Dynamic Range from 0.1 to 9Amps

¨   Meets IEC62053-21 class 1

¨   Meets IEC 60044-1 class 0.1 Phase error < 5'

¨   Very low temperature coefficient

¨   Meets UL class B (130℃) thermal insulation system

¨   Meets UL 94V-0

¨   AC isolation resistance: 4KV for 60s


Application


•   Electricity meter

•   Recording

•   Power monitoring

•   Energy management

•   Alternative energy monitoring



ELECTRIC SPECIFICAITON AT 25

Model number

Turns Ration

Ipri4

Iout5

Iprimax6

Ioutmax7

RS

Accuracy

Class3

RL8

    Weight

Frequency range

    Amps

 mA

Amps

mA

Ohms


Ohms

     (g)

  (Hz)

     LO-EM0003

     1:300

    1.5

5

9

30


0.1

20

      20

   50-60

Note:

1.Output voltage is proportional to the derivative(di/dt)of the input current based on the Rogowski Coil principle.

2.All current and voltages assumed to be sinusoidal waveforms at Fr, the constant rated frequency in Hz, measured as RMS value.

3.Accuracy class per IEC60044-1Table 11.

4.Ipri=Rated primary current.

5.Iout=Rated secondary current.

6.Iprimax=Sensed max primary current.

7.Loutmax=Sensed max secondary current.

8.RL=Terminating resistance. Varying terminating resistance increases or decreases output Voltage /Ampers according to following

equation RL=Vout*Nsec/Ipri



ABSOLUTE MAXIMUM RATINGS

Operating free air temperature range

-40 to 85

Storage temperature range

-40 to 125

LEADS INFORMATION

UL1007 26AWG Black &White

Leads length:135±5mm

Stripped and tinned

5±2mm

56

Mechanical Specifications:

LO-EM0003 DIMENSIONS

In order to ensure that High Quality Current Sensor Transformer with Slight Drift are advanced in technology, superior in quality and reasonable in price, our company has made great efforts in product management. If needed, welcome to help make speak to with us by our web page or cellular phone consultation, we are going to be delighted to serve you. With increasing competition in the market, more and more companies have improved their competitiveness with high-quality, personalized products and services.

Hot Tags: Current Sensor Transformer used for high precision current measuring, China, manufacturers, customized, quotation, low price, made in China, Miniature Split Core Current Transformers, Split Core Current Transducer, Planar Transformer 28 2V Lo Plt8088 008, 200A 5A Center Through Current Transformer, High range Current Transformers, 1 2500 DC Immune Current Transducer