Preventive Measures for Current Transformer Open Circuit
Sep 20, 2023| It is clearly stipulated in the electrical safety work regulations that the secondary line side of the current transformer must be reliably grounded. The purpose is to prevent the high voltage of the primary side insulation from entering the secondary side, causing harm to people and secondary side instruments. Therefore, the secondary line side of the current transformer must be reliably grounded.
When the secondary open-circuit fault of the current transformer occurs, the correct and safe way to deal with it is to cut off the power on the high-voltage side and then handle it (restore the open-circuit point to the normal loop state), but this will cause unplanned power outage;
The unconventional treatment method is: when the current transformer is open, there is a discharge phenomenon at the open circuit point, which is easier to find. A wire can be used (the wire diameter must meet the rated secondary current requirements of the current transformer. Generally, the rated secondary current of the current transformer is 1 A or 5 A, and it is completely OK to use a 2 square wire). First, connect one end of the wire to the open coil After the grounding terminal is well connected, use an insulating tool (the insulation of a general screwdriver handle will suffice) to connect the other end of the wire to a fixed connection point far away from the open circuit point to achieve the purpose of short-circuiting the open circuit point. At this time, it will be easier This method is not recommended from a safety perspective to handle open circuit points to avoid equipment power outages. However, in order to avoid assessment accidents, it can be completed by experienced secondary system staff.
Prevention of open circuit of secondary circuit of current transformer:
(1) Short-circuit protection equipment such as fuses is not allowed to be installed in the secondary circuit of the current transformer;
(2) The secondary circuit of the current transformer is generally not switched. When switching is necessary, there should be reliable measures to prevent open circuit;
(3) Current transformers are generally not suitable for relay protection and measuring instruments. When they must be used together, the measuring instruments must be connected through an intermediate current transformer;
(4) For current transformers that have been installed but not in use, the terminals of the secondary windings must be short-circuited and grounded.
(5) The terminals of the secondary circuit of the current transformer should use test terminals
(6) It should be ensured that the connecting wire of the secondary circuit of the current transformer has sufficient mechanical strength.